Detailed Product Description
-
IEC, DIN 1KV ~ 26 / 35KV PVC insulated power cable for transmission and distribution
-
Product standard
The product is manufactured according to the standard of GB/T12706-2002, GB/T18380.3-2001, GB/T17650-1998 and GB/T17651-1998 or IEC and DIN and ICEA.
The product is suitable for power transmission and distribution lines with rated voltage 0.6/1 KV~26/35KV.
-
Operating characteristics
Rated power frequency voltage U0/U: 0.6/1KV~26/35KV.
PVC insulated power cable Max. permissible continuous operating temperature of the conductor should not exceed 70℃, XLPE permissible continuous operating temperature of the conductor should not exceed 90℃.
Max. Short-circurrt temperature of conductor shall not exceed: PVC insulation 160℃, XLPE insulation 250℃. (5s maximum duration)
The installation temperature should not below 0℃
The flame-retardant properties of cable comply with the requirements specified in A kind of GB/T18380.3-2001
The flame-retardant properties of lower halogen cable comply with requirements specified in A kind of GB/T18380.3-2001 except complying with requirements specified in GB/T17651.2-1998.
The flame-retardant properties of no halogen cable comply with requirements specified in A kind of GB/T18380.3-2001 except complying with requirements specified in GB/T17651.2-1998. and GB/T17651-1998.
Three bending radius of a single core should not less than 20 times of the cable diameter.
Two bending radius of a three-core cable should not less than 15 times of the cable diameter.
The rated voltage of the cable for a given application shall be suitable for the operating condition in the system in which the cable is used, and is expressed in the form of U0/U (Um) are applied to the system voltages and running state, and expressed in the form U0/U (Um).
U0—The rated power-frequency voltage between conductor and earth or metallic screen, for which the cable designed.
U—The rated power-frequency voltage between conductors for which the cable designed.
Um—The maximum value of “the highest system voltage” for which the equipment may be used.
-
The values U0 recommended for cables to be used in three-phase systems are listed below
|
U
KV
|
Um
KV
|
U0*
|
|
A&B system
|
System categories C
|
|
1
|
1.2
|
0.6
|
0.6
|
|
3
|
3.6
|
1.8
|
3.6
|
|
6
|
7.2
|
3.6
|
6
|
|
10
|
12
|
6
|
8.7
|
|
15
|
17.5
|
8.7
|
12
|
|
20
|
24
|
12
|
18
|
|
35
|
40.5
|
21
|
26
|
The first cable-suitable for one single-phase ear thing-block time does not exceed one minute each time. Max. time not exceed 8 hours, and not exceed 125 hours in all in one year.
The second class cable-suitable for more the ear thing-block time and more better insulated performa.