Parallel Bunched Aerial Insulated Cable

■ Product standard
Enterprise standard , Refer to“Chosen and used technical condition of parallel clustered aerial insulation cable” issued by Department of Agricultural Work , State Electric Power Corporation.
■ Application
The parallel clustered aerial insulation cable with 0.6/1kV rated voltage and below can be wide used for low voltage electric distribution system at country .This cable features good weather ability , anti-ageing , less wire loss , simple in construction , short time limit for project and can prevent effectively from electric larceny and creepage , etc phenomenon and has better safe property.
■ Operating characteristics
1. Rated voltage U0/U: 0.6/1kv
2. Max. permissible continuous temperature:
PVC,PE insulated aerial cables:70℃; XLPE insulated aerial cables:90℃
3. Max. short-circuit temperature of the conductor shall not exceed:
PVC insulated aerial cables:160℃; PE insulated aerial cables:130℃; XLPE insulated aerial cables:250℃.
4. The installation ambient temperature:
PE, XLPE≥-20℃; PVC≥0℃
■ Type of cable
|
Type
|
Name
|
|
BS-JKV-0.6/1
|
Rated voltage 0.6/1kV Copper-conductor , PVC insulated and Parallel bunched aerial insulated cable
|
|
BS-JKLV-0.6/1
|
Rated voltage 0.6/1kV Aluminum-conductor , PVC insulated and Parallel bunched aerial insulated cable
|
|
BS-JKY-0.6/1
|
Rated voltage 0.6/1kV Copper-conductor , PE insulated and Parallel bunched aerial insulated cable
|
|
BS-JKLY-0.6/1
|
Rated voltage 0.6/1kV Aluminum-conductor , PE insulated and Parallel bunched aerial insulated cable
|
|
BS-JKYJ-0.6/1
|
Rated voltage 0.6/1kV Copper-conductor , XLPE insulated and Parallel bunched aerial insulated cable
|
|
BS-JKLYJ-0.6/1
|
Rated voltage 0.6/1kV Aluminum-conductor , XLPE insulated and Parallel bunched aerial insulated cable
|
■ Production range of cable
|
Type
|
No. of cores
|
Rated Voltage kV
|
Nominal cross-sectional mm2
|
|
BS-JKV,BS-JKY, BS-JKYJ
|
2
|
0.6/1
|
2.5~70
|
|
BS-JKLV,BS-JKLY, BS-JKLYJ
|
4—120
|
|
BS-JKV,BS-JKY, BS-JKYJ
|
4
|
2.5~70
|
|
BS-JKLV,BS-JKLY, BS-JKLYJ
|
4—70
|
|
BS-JKV,BS-JKY, BS-JKYJ
|
3+1
|
6~120
|
|
BS-JKLV,BS-JKLY, BS-JKLYJ
|
6—120
|
■ Construction and main technical data
|
BS two-core constant section of parallel clustered aerial insulated cable
|
|
Number and nom. Cross-section of conductors mm2
|
Min. No. of a signal wire in conductor
|
Diameter of Conductor
mm
|
insulation
thickness
mm
|
Max. D.C. resistance of copper conductor (20℃)Ω/km
|
Min. insulation resistance of rated work temperature
Ω. km
|
Single Tensile force of cable
N
|
Cable calculated Weight
|
XLPE Current
Carrying (40℃)A
|
|
PVC insulated
|
XLPE insulated
|
|
Kg/km
|
|
Cu
|
Al
|
Cu
|
Al
|
PVC
insulated
|
XLPE
insulated
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
|
2×2.5
|
1
|
—
|
1.78
|
1.0
|
7.41
|
—
|
0.012
|
1.20
|
1914
|
—
|
74
|
—
|
64
|
—
|
32
|
—
|
|
2×4
|
1
|
1
|
2.26
|
1.0
|
4.61
|
7.39
|
0.010
|
1.00
|
3009
|
1337
|
105
|
56
|
94
|
45
|
42
|
31
|
|
2×6
|
1
|
1
|
2.76
|
1.0
|
3.08
|
4.91
|
0.007
|
0.70
|
4457
|
1927
|
146
|
72
|
133
|
59
|
49
|
40
|
|
2×10*
|
6
|
6
|
3.80
|
1.0
|
1.83
|
3.08
|
0.007
|
0.67
|
6942
|
3300
|
230
|
108
|
213
|
90
|
71
|
55
|
|
2×16*
|
6
|
6
|
4.80
|
1.2
|
1.15
|
1.91
|
0.007
|
0.65
|
10972
|
5024
|
363
|
165
|
337
|
139
|
97
|
75
|
|
2×25*
|
6
|
6
|
6.00
|
1.2
|
0.727
|
1.20
|
0.005
|
0.54
|
16930
|
7524
|
541
|
232
|
509
|
200
|
128
|
100
|
|
2×35*
|
6
|
6
|
7.00
|
1.4
|
0.524
|
0.868
|
0.005
|
0.54
|
23462
|
10354
|
751
|
319
|
709
|
276
|
158
|
122
|
|
2×50*
|
6
|
6
|
8.40
|
1.4
|
0.387
|
0.641
|
0.005
|
0.46
|
33004
|
14022
|
1035
|
416
|
987
|
368
|
194
|
148
|
|
2×70*
|
12
|
6
|
10.0
|
1.4
|
0.268
|
0.443
|
0.004
|
0.40
|
46922
|
20708
|
1416
|
551
|
1360
|
494
|
240
|
189
|
|
2×95*
|
115
|
12
|
11.6
|
1.6
|
0.193
|
0.320
|
0.004
|
0.39
|
63518
|
27454
|
1914
|
738
|
1840
|
664
|
296
|
230
|
|
2×120*
|
18
|
15
|
13.0
|
1.6
|
0.153
|
0.253
|
0.004
|
0.35
|
79822
|
34678
|
2378
|
892
|
2298
|
812
|
347
|
270
|
|
*Compacted rotundity conductor
|

|
BS four-core constant section of parallel clustered aerial insulated cable
|
|
Number and nom. Cross-section of conductors mm2
|
Min. No. of a single wire in conductor
|
Diameter of Conductor
mm
|
Insulation
thickness
mm
|
Max. D.C. resistance of copper conductor (20℃)Ω/km
|
Min. insulation resistance of rated work temperature
Ω. km
|
Single Tensile force of cable
N
|
Cable calculated Weight
|
XLPE Current
Carrying (40℃)A
|
|
PVC insulated
|
XLPE insulated
|
|
Kg/km
|
|
Cu
|
Al
|
Cu
|
Al
|
PVC
insulated
|
XLPE
insulated
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
|
4×2.5
|
1
|
—
|
1.78
|
1.0
|
7.41
|
—
|
0.012
|
1.20
|
3828
|
—
|
149
|
—
|
129
|
—
|
29
|
—
|
|
4×4
|
1
|
1
|
2.26
|
1.0
|
4.61
|
7.39
|
0.010
|
1.00
|
6050
|
2675
|
213
|
113
|
190
|
90
|
40
|
29
|
|
4×6
|
1
|
1
|
2.76
|
1.0
|
3.08
|
4.91
|
0.007
|
0.70
|
8938
|
3853
|
293
|
146
|
267
|
119
|
45
|
37
|
|
4×10*
|
6
|
6
|
3.80
|
1.0
|
1.83
|
3.08
|
0.007
|
0.67
|
13884
|
6600
|
463
|
217
|
428
|
181
|
59
|
46
|
|
4×16*
|
6
|
6
|
4.80
|
1.2
|
1.15
|
1.91
|
0.007
|
0.65
|
21944
|
10048
|
730
|
334
|
677
|
281
|
79
|
63
|
|
4×25*
|
6
|
6
|
6.00
|
1.2
|
0.727
|
1.20
|
0.005
|
0.54
|
33860
|
15048
|
1087
|
468
|
1022
|
403
|
104
|
83
|
|
4×35*
|
6
|
6
|
7.00
|
1.4
|
0.524
|
0.868
|
0.005
|
0.54
|
46924
|
20708
|
1510
|
643
|
1423
|
556
|
130
|
101
|
|
4×50*
|
6
|
6
|
8.40
|
1.4
|
0.387
|
0.641
|
0.005
|
0.46
|
66008
|
28004
|
2071
|
833
|
1975
|
737
|
158
|
126
|
|
4×70*
|
12
|
6
|
10.0
|
1.4
|
0.268
|
0.443
|
0.004
|
0.40
|
93844
|
41416
|
2834
|
1101
|
1101
|
979
|
202
|
158
|
|
*Compacted rotundity conductor 
|
|
3+1 cores constant section of parallel clustered aerial insulated cable
|
|
Number and nom. Cross-section of conductors mm2
|
Min. No. of a single
wire in conductor
|
Diameter of conductor mm
|
Insulation
thickness
mm
|
Max.D.C.resistance of copper conductor (20℃) Ω/km
|
Min. insulation resistance of rated work temperature
Ω. km
|
Single Tensile force of cable
N
|
Cable calculated Weight
|
XLPE Current carrying (40℃)A
|
|
PVC
insulated
|
XLPE insulated
|
|
Cu
|
Al
|
Kg/km
|
|
Main
core
|
Fourthly
core
|
Main
core
|
Fourthly
core
|
Main
core
|
Fourthly
core
|
Main
core
|
Fourthly
core
|
Cu
|
Al
|
PVC
insu- lated
|
XLPE
insu- lated
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
Cu
|
Al
|
|
3×6+1×4
|
1
|
1
|
1
|
1
|
2.76
|
2.76
|
1.0
|
1.0
|
3.080
|
4.910
|
0.007
|
0.700
|
8190
|
3552
|
274
|
138
|
248
|
112
|
49
|
—
|
|
3×10+ 1×6*
|
6
|
1
|
6
|
1
|
3.80
|
2.76
|
1.0
|
1.0
|
1.830
|
3.080
|
0.007
|
0.670
|
13828
|
5281
|
421
|
198
|
388
|
165
|
59
|
|
|
3×16+ 1×10*
|
6
|
6
|
6
|
6
|
4.80
|
3.80
|
1.2
|
1.2
|
1.150
|
1.910
|
0.007
|
0.650
|
19929
|
9186
|
670
|
311
|
619
|
260
|
79
|
|
|
3×25+1×16*
|
6
|
6
|
6
|
6
|
6.00
|
4.80
|
1.2
|
1.2
|
0.727
|
1.200
|
0.005
|
0.540
|
30886
|
13798
|
998
|
453
|
936
|
373
|
104
|
|
|
3×35+1×25*
|
6
|
6
|
6
|
6
|
7.00
|
6.00
|
1.4
|
1.2
|
0.524
|
0.868
|
0.005
|
0.540
|
43658
|
19293
|
1414
|
609
|
1329
|
524
|
130
|
|
|
3×50+1×35*
|
6
|
6
|
6
|
6
|
8.40
|
7.00
|
1.4
|
1.4
|
0.387
|
0.641
|
0.005
|
0.446
|
61237
|
26210
|
1937
|
792
|
1841
|
696
|
158
|
|
|
3×70+ 1×50*
|
12
|
6
|
12
|
6
|
10.0
|
8.40
|
1.4
|
1.4
|
0.268
|
0.443
|
0.004
|
0.400
|
86885
|
38073
|
2655
|
1045
|
2542
|
932
|
202
|
|
|
3×95+1×70*
|
15
|
12
|
15
|
12
|
11.0
|
10.0
|
1.6
|
1.6
|
0.193
|
0.320
|
0.004
|
0.390
|
118738
|
51535
|
3606
|
1409
|
3458
|
1261
|
248
|
|
|
3×120+1×95*
|
18
|
15
|
15
|
15
|
13.0
|
11.6
|
1.6
|
1.6
|
0.153
|
0.253
|
0.004
|
0.350
|
151492
|
65744
|
4520
|
1704
|
4364
|
1548
|
202
|
|
|
*Compacted rotundity conductor
|